HAKAN ALTIN-ELEKTRİK VE ELEKTRONİK MÜHENDİSİ
🏠︎

OVERHEAD   LİNE   TEMPERATURE-WIND BASED   TENSION-SAG   CALCULATION

Over Head Line Temperature-Wind Speed Based  Tension-Sag  Calculation According to 5 Ice Load Zone In Türkiye

1. STATE (REFERANCE)

1091,53
1,4141
8000
0,0000191

2. STATE (Change)

715,12
0,8186
0,0000191
                                
 

Temperature-Wind-Tension-Sag:

Pole Span: 180 m  Ruling Span a_ort = 160 m Air Temperature =5°C   ve Wind Speed =29,12 m/sn için Tension-Sag Calculation
 
Tension: 715,12 kg Tension: 715,12 kg fmax: 4,64 m Hground: 8,36 m Pole Length =13 m Pole Length =13 m Suspension Pole Length =14 m (Pole length Selected According to 5 Ice Load Zone Condition in Türkiye.)

Click here for Temperature-Wind Dependent Field Conductor Tension Table Values.