HAKAN ALTIN -Elektrik ve Elektronik Mühendisi
      🏠︎        3 Pole HV Electrıcıty Overhead Distribution Lıne Uplıft Control (Based on X, Y, Z Coordinate Values.)
Coductor and Regional Mechanical Parameters :
  m   kg/m   kg
1. Pole Parameter (T1 - Tension)
2. Pole Parameter  (C2 - Suspension)
3. Pole Parameter (T3 - Tension)

PIGEON (3x3/0) Conductor    3.Bolge  Lowesr Temperature = -25 0C  Sr=156,38 m  Tension Strength = 469,2 kg ve Conductor Weight w2 =0,3429 kg/m take into account;(Eski)
a1 Span Length (Projection)141,99 m
a2 Span Length (Projection)167,61 m
Ruling Menzil (aᵣ)156,38 m
h1 Height  (Altitu Differance)1,85 m
h2 Height  (Altitu Differance)23,16 m
X_proje (Geometric)6,54 m
f_min (Min Flesh)8,70 m
Differ (f_min - X_proje)2,16 m
🟢 fmin > xproje olduğundan Up Lift yoktur (f_min: 8,7 > X_proje: 6,54)
   Saha Profil Çizimi
🟢 Green Line: Terrain Profile White/Yellow: Pole 🔵 Thin Blue Line: f_min Curve 🔴 Pink Vertical: X_proje Height