Coductor and Regional Mechanical Parameters :
m
kg/m
kg
1. Pole Parameter (T1 - Tension)
2. Pole Parameter (C2 - Suspension)
3. Pole Parameter (T3 - Tension)
PIGEON (3x3/0)
Conductor 3.Bolge Lowesr
Temperature = -25 0C Sr=156,38
m
Tension Strength = 469,2 kg ve
Conductor Weight w2 =0,3429
kg/m take into account;(Eski)
| a1 Span Length (Projection) | 141,99 m |
| a2 Span Length
(Projection) | 167,61 m |
| Ruling Menzil (aᵣ) | 156,38 m |
| h1 Height
(Altitu Differance) | 1,85 m |
| h2 Height
(Altitu Differance) | 23,16 m |
| X_proje (Geometric) | 6,54 m |
| f_min (Min Flesh) | 8,70 m |
| Differ (f_min - X_proje) | 2,16 m |
🟢 fmin > xproje olduğundan Up Lift yoktur (f_min: 8,7 > X_proje: 6,54)