HAKAN ALTIN-ELEKTRİK VE ELEKTRONİK MÜHENDİSİ

 🏠︎

KabloSec Pro v6.5

Underground Cable Analysis Softwareı

Calculated Current 168 A
1. Project and Load Defınıtıons
3. System Preferences
Copper (pvc) Cable Analysıs
3x95+50mm²
Corrected Cable Current Capacıty ( 199 / 233 A)
Actıve %e 1,6
Reactıve %e 0,37
Total %e % 1,97
Fuse 200 A

Capacıty Control: 199>  168 A

Total Voltage Drop 1,97<3

ANALYSIS RESULT: MEETING CRITERIA

Aluminum (pvc) Cable  Analysis
3x120+70mm²
Corrected Calculated Current Capacity (179 / 210 A )  
Actıve %e 2,03
Reactıve %e 0,36
Total %e % 2,39
Fuse 200 A

 Capacıty Control: 179 >  168 A Total Voltage Drop 2,39 < 3

ANALYSIS RESULT: MEETING CRITERIA
K1(C)-XLP/PVC 0,93/0,89
K2 (soil) 1
K3 (Depth) 0,96
prepared by Hakan ALTIN