Transformer Column Cable, Grounding Conductor Selection - Underground Cable Selection  

-Click here for detailed underground cable calculations and report.

-Solar Power Plant Projects AC-DC cable cross-section, fuse, circuit breaker, surge arrester, busbar, current transformer, and relay  selection calculations. Click This

 

         
   Transformer Power(kVA):    

                 Impedance     Cu 56  Al 35 

XLP    PVC  
Cos φ =       φ = 30,68 Cable Laying in Earth Channel:    xlpe pvc
Secondary Voltage:    Cable Temp. Derating Factor(K1):  0,82  0,71
Short Circuit Impedance%: Earth Temp Derating Factor(K2):  0,93  0,89
Ambient Temperature(k1): Nature of Soil Derating Factor(K3):  1  
Soil Temperature(k2): Earth Laying Depth Rating Factor(K4):  0,96  
Nature of Soil(k3): Target Voltage Drop(%Δu.):  
Laying Depth(k4): Underground Cable Output Power(kW):     A  
Secondary Rated Current(A):  2309,4 Cable Length(m):    
Secondary Short Circuit Current(A):  38.490,00 Number of Circuits(Number):       Duct:  
Number of Column Cables for Each: Phase(Number):      Copper Aluminium
Neutral Grounding Cable Cross Section:   Selected Cross-Section(xlp):  3x95+50 ( 230 / 253 A)  3x120+70 (205 / 225 A )
Copper   (mm2):  189 mm2 ;Seçilen Kablo :240 mm2 Selected Fuse:  200  A  200 A
Aluminium   (mm2):  290 mm2 Δu.akt  6,08  7,71
Steel  (mm2):  523 mm2 u.akt  1,6  2,03
    Δu.r  1,39  1,37
    Transformer Column Cable   u.r   0,37  0,36

             PVC: Copper              Aluminium

     XLPE Copper        Aluminium

%et

 1,97  2,39
 9x(1X240 )

 11x(1X240 )

   6x(1X240 )

 8x(1X240 )

     

 

 

 

   

                                                                                                    

   

-Cable current carrying capacities and cable cross-section selection are made according to IEC 60502-I Direct in Ground (30 deg. C), Direct in Duct (30 deg. C).Thermal resistivity of soil=150 deg. C cm/W

**Aluminum grounding conductor can be laid inside the building. It cannot be laid in the ground.

**In our facilities, instead of copper material in column cables and grounding conductors, Aluminum can be used as column cable and braided steel wire can be used as grounding conductor.

*** The cross-section of the neutral conductor at a distance of 20 m from the protective grounding has been calculated.

****In our facilities, the cross-section of the protection grounding may be equal to or larger than the neutral grounding conductor cross-section. Click for detailed calculations.